Fire Performance of Electric Cables

Often the most effective flame retardant cables are halogenated as a end result of each the insulation and outer Jacket are flame retardant however once we need Halogen Free cables we find it is often solely the outer jacket which is flame retardant and the inner insulation just isn’t.
This has significance because whereas cables with a flame retardant outer jacket will usually move flame retardance exams with external flame, the same cables when subjected to excessive overload or prolonged brief circuits have proved in university exams to be highly flammable and can even start a fireplace. This impact is thought and published (8th International Conference on Insulated Power Cables (Jicable’11 – June 2011) held in Versailles, France) so it is perhaps stunning that there are no widespread check protocols for this seemingly frequent occasion and one cited by both authorities and media as cause of building fires.
Further, in Flame Retardant take a look at methods similar to IEC60332 parts 1 & 3 which make use of an external flame source, the cable samples aren’t pre-conditioned to normal working temperature however tested at room temperature. This oversight is important particularly for power circuits as a result of the temperature index of the cable (the temperature at which the cable materials will self-support combustion in regular air) shall be considerably affected by its beginning temperature i.e.: The hotter the cable is, the more easily it’ll propagate fireplace.
It would seem that a need exists to re-evaluate present cable flame retardance check methods as these are generally understood by consultants and customers alike to supply a dependable indication of a cables capability to retard the propagation of fireside.
If we can’t trust the Standards what will we do?

In the USA many constructing standards do not require halogen free cables. Certainly this isn’t as a result of Americans usually are not wisely informed of the dangers; somewhat the strategy taken is that: “It is better to have extremely flame retardant cables which do not propagate hearth than minimally flame retardant cables which can unfold a fire” – (a small fire with some halogen may be higher than a large fireplace with out halogens). One of one of the best ways to make a cable insulation and cable jacket extremely flame retardant is through the use of halogens.
Europe and plenty of international locations around the world undertake a different mentality: Halogen Free and Flame Retardant. Whilst this is an admirable mandate the truth is rather totally different: Flame propagation exams for cables as adopted in UK and Europe can arguably be mentioned to be much less stringent than some of the flame propagation checks for cables in USA leading to the conclusion that widespread tests in UK and Europe could simply be tests the cables can pass rather than checks the cables ought to move.
Conclusion

For most flexible polymeric cables the choice stays at present between high flame propagation efficiency with halogens or lowered flame propagation efficiency with out halogens.
Enclosing cables in metal conduit will cut back propagation on the point of fireside however hydrocarbon based mostly combustion gasses from decomposing polymers are probably propagate via the conduits to switchboards, distribution boards and junction boxes in different components of the building. Any spark such because the opening or closing of circuit breakers, or contactors is prone to ignite the combustible gasses leading to explosion and spreading the fireplace to a different location.
While MICC (Mineral Insulated Metal Sheathed) cables would provide a solution, there could be typically no singe perfect reply for each installation so designers need to judge the required performance on a “project-by-project” foundation to resolve which technology is optimal.
The main significance of fireplace load

Inside all buildings and initiatives electrical cables present the connectivity which keeps lights on, air-conditioning working and the lifts running. It powers computers, workplace gear and offers the connection for our phone and computers. Even our mobile phones need to connect with wi-fi or GSM antennas that are linked to the telecom community by fiber optic or copper cables. Cables ensure our safety by connecting

fire alarms, emergency voice communication, CCTV, smoke shutters, air pressurization followers, emergency lighting, hearth sprinkler pumps, smoke and warmth detectors, and so many different options of a contemporary Building Management System.
Where public safety is necessary we frequently request cables to have added security features corresponding to flame retardance to ensure the cables don’t simply spread hearth, circuit integrity during fire so that essential fire-fighting and life safety equipment hold working. Sometimes we may recognize that the combustion of electric cables produces smoke and this could be poisonous so we name for cables to be Low Smoke and Halogen Free. Logically and intuitively we expect that by requesting these particular properties the cables we buy and set up shall be safer

Because cables are put in by many various trades for different purposes and are largely hidden or embedded in our constructions, what is often not realized is that the many miles of cables and tons of plastic polymers which make up the cables can symbolize one of the greatest hearth hundreds in the building. This point is actually price pondering extra about.
PVC, XLPE, EPR, CSP, LSOH (Low Smoke Zero Halogen) and even HFFR (Halogen Free Flame Retardant) cable supplies are mostly primarily based on hydrocarbon polymers. These base materials usually are not generally flame retardant and naturally have a high fireplace load. Cable producers make them flame retardant by including compounds and chemicals. Certainly this improves the volatility of burning however the gas content material of the bottom polymers remains.
Tables 1 and a couple of above evaluate the fire load in MJ/Kg for common cable insulating supplies against some widespread fuels. The Heat Release Rate and volatility in air for these materials will differ however the gasoline added to a hearth per kilogram and the consequential volume of heat generated and oxygen consumed is relative.
The quantity in kilometers and tons of cables put in in our buildings and the associated fireplace load of the insulations is considerable. This is especially necessary in tasks with long egress instances like excessive rise, public buildings, tunnels and underground environments, airports, hospitals etc.
When contemplating fireplace security we should first understand an important components. Fire specialists inform us most fireplace associated deaths in buildings are brought on by smoke inhalation, temperature rise and oxygen depletion or by trauma attributable to jumping in making an attempt to flee these results.
Smoke

The first and most necessary facet of smoke is how much smoke? Typically the larger the fireplace the more smoke is generated so something we can do to minimize back the unfold of fire may also correspondingly scale back the amount of smoke.
Smoke will include particulates of carbon, ash and other solids, liquids and gasses, many are poisonous and flamable. In specific, fires in confined areas like buildings, tunnels and underground environments cause oxygen ranges to drop, this contributes to incomplete burning and smoldering which produces increased amounts of smoke and poisonous byproducts including CO and CO2. Presence of halogenated supplies will release toxic Halides like Hydrogen Chloride along with many other toxic and flammable gasses in the smoke.
For this reason common smoke checks carried out on cable insulation materials in massive three meter3 chambers with loads of air can present deceptive smoke figures because complete burning will typically launch considerably less smoke than partial incomplete burning which is probably going in practice. Simply specifying IEC 61034 with a defined obscuration value then thinking this will provide a low smoke environment throughout hearth might sadly be little of assist for the individuals really involved.
Halogens, Toxicity, Fuel Element, Oxygen Depletion and Temperature Rise

It is regarding that Europe and other international locations undertake the idea of halogen free materials with out properly addressing the topic of toxicity. Halogens released during combustion are extremely toxic but so too is carbon monoxide and this is not a halogen gas. It is common to name for halogen free cables and then allow using Polyethylene because it is halogen free. Burning Polyethylene (which may be seen from the table above has the highest MJ gasoline load per Kg of all insulations) will generate virtually 3 occasions extra heat than an equivalent PVC cable. This means is that burning polyethylene won’t only generate virtually 3 instances extra warmth but additionally devour nearly 3 occasions extra oxygen and produce significantly more carbon monoxide. Given carbon monoxide is responsible for most toxicity deaths in fires this example is at best alarming!

The fuel parts proven within the table above indicate the quantity of heat which might be generated by burning 1kg of the frequent cable insulations tabled. Certainly this heat will accelerate the burning of different adjacent supplies and should help spread the fireplace in a constructing but importantly, so as to generate the warmth power, oxygen needs to be consumed. The higher the warmth of combustion the more oxygen is needed, so by choosing insulations with excessive gasoline parts is including significantly to a minimum of four of the first risks of fires: Temperature Rise, Oxygen Depletion, Flame Spread and Carbon Monoxide Release.
Perhaps it’s best to put in polymeric cables inside steel conduits. This will definitely help flame unfold and decrease smoke as a result of inside the conduit oxygen is limited; however this isn’t an answer. As stated previously, many of the gasses from the decomposing polymeric insulations contained in the conduits are extremely flammable and poisonous. These gases will migrate along the conduits to junction packing containers, switch panels, distribution boards, motor management centers, lamps, switches, and so forth. On entering the gases can ignite or explode with any arcing such because the make/break of a circuit breaker, contactor, switch or relay causing the hearth to spread to another location.
digital pressure gauge of “Halogen Free” whereas ignoring the opposite poisonous elements of fireplace is a clear admission we do not perceive the topic nicely nor can we simply define the dangers of combined poisonous parts or human physiological response to them. It is necessary however, that we do not continue to design with solely half an understanding of the issue. While no perfect resolution exists for organic based cables, we will certainly reduce these critically necessary results of fireplace risk:
One choice perhaps to determine on cable insulations and jacket supplies which are halogen free and have a low gas factor, then set up them in metal conduit or possibly the American method is better: to use highly halogenated insulations so that in case of fire any flame unfold is minimized.
For most energy, control, communication and data circuits there is one complete solution obtainable for all the issues raised on this paper. It is an answer which has been used reliably for over 80 years. MICC cables can provide a total and complete answer to all the issues related to the hearth safety of organic polymer cables.
The copper jacket, magnesium oxide insulation and copper conductors of MICC ensure the cable is effectively fire proof. MICC cables have no natural content so simply can not propagate flame or generate any smoke. The zero gas load ensures no warmth is added and no oxygen is consumed.
Being inorganic MICC cables can not generate any halogen or toxic gasses at all including CO.
Unfortunately many common cable fire check methods used right now could inadvertently mislead folks into believing the polymeric versatile cable merchandise they purchase and use will perform as anticipated in all fireplace conditions. As outlined on this paper, sadly this may not be appropriate.
For more information, go to www.temperature-house.com